Rated supply voltage |
100 – 277 V |
交流电压范围 |
100 – 320 V |
Mains frequency |
50 / 60 Hz |
Mode of protection |
L-N |
AC system |
TN, TT or IT |
Type 2 surge protection (T2) |
是 |
Type 3 surge protection (T3) |
是 |
Rated load current |
16 A |
Nominal discharge current (8/20 µs) |
5 kA |
Max. discharge current (8/20 µs) |
10 kA |
Combination wave (1.2/50 µs) |
10 kV (5 kA) |
Short-circuit current rating |
3 kA |
Voltage protection level (at nominal discharge current (8/20 µs) and at 6 kV (1.2/50 µs)) |
≤ 1.3 kV |
Residual voltage (at nominal discharge current (8/20 µs) and at combination wave (1.2/50 µs)) |
≤ 1.3 kV |
TOV behavior (5 s / withstand mode) |
400 V AC |
TOV behavior (120 min. / safe failure mode) |
528 V AC |
Response time |
≤ 25 ns |
Max. backup fuse (MCB type B and C) |
16 A |
环境温度 ta |
-40 ... +80 °C |
Storage temperature ts |
-40 ... +80 °C |
保护类型 |
IP20 |
Altitude (above sea level) |
≤ 2,000 m |
尺寸 长 x 宽 x 高 |
56 x 36.5 x 34 mm |